Hipotronics 2293 Automatic Transformer Winding Analyzer, 264VAC, 1kW

Do you have a Hipotronics 2293 Automatic Transformer Winding Analyzer, 264VAC, 1kW you want to sell?

We buy used equipment! Learn about selling

Image Coming Soon

Hipotronics 2293 Automatic Transformer Winding Analyzer

The Hipotronics 2293 is a state-of-the-art Automatic Transformer Winding Analyzer designed to streamline the testing process for power and distribution transformers. This advanced instrument combines multiple testing functionalities into one compact unit, providing essential measurements swiftly and accurately.

Key Features:

    • Multipurpose Functionality: Conducts winding resistance, turns ratio, core demagnetisation, transformer type detection, and heat run tests (cooling curve) efficiently.
    • Simplified Setup: Experience a one-time-connection system that drastically reduces measurement time and allows all tests to be performed in sequence without the need for reconnections.
    • User-Friendly Interface: Intuitive touch screen with full graphical visualization for easy navigation and control of various testing operations.
    • Simultaneous Winding Magnetisation: Features a unique method for winding resistance measurements, capable of achieving test currents up to 100 A, ensuring reliability akin to traditional equipment.
    • Advanced Measurement Techniques: Sophisticated procedures for precise turns ratio and phase displacement measurements.
    • Demagnetisation Function: The transformer is automatically returned to a demagnetised state after testing, preserving its operational integrity.
    • Data Management: Facilitates data transfer via USB memory drives or LAN connections for seamless record-keeping.
    • Versatile Applications: An indispensable tool for factory tests, acceptance tests, and regular maintenance on various transformer types, including power and distribution transformers, as well as all high-voltage (HV) windings.

Specifications:

  • Resistance Measurement:
      • Maximum Measuring Current DC: 32 A (user selectable)
      • Maximum Charging Voltage DC: 100 V
      • Measurement Range: 0.1 µΩ - 300 kΩ
    • Accuracy:
        • 0.1 µΩ - 300 µΩ: Accuracy: 0.1% ± 0.5 µΩ
        • 300.1 µΩ - 30 kΩ: Accuracy: 0.1%
        • 30.01 kΩ - 300 kΩ: Accuracy: 1%
  • Ratio Measurement:
      • Maximum Supply Current AC: 1 APeak/700mARMS
      • Maximum Measuring Voltage AC: 95 VPeak/67 VRMS
      • Measurement Range: 1.0 - 100,000
    • Accuracy:
        • 1.0 - 100: Accuracy: 0.05%
        • 100 - 2,000: Accuracy: 0.1%
        • 2,000 - 20,000: Accuracy: 1%
        • 20,000 - 100,000: Accuracy: 5%
    • Phase Measurement Accuracy:
        • 1.0 - 500: Typical Accuracy: ±0.25°
        • 500 - 10,000: Typical Accuracy: ±1.00°
  • Mains Power Supply:
      • Voltage: 90 VAC - 264 VAC
      • Maximum Power: 1000 W
      • Frequency: 47 Hz - 63 Hz

How can we help you with today?